Shell Diala S2 ZU-I ngt is a high-quality, uninhibited insulating oil formulated from highly refined mineral oils, offering superior oxidation stability, low temperature fluidity, and strong dielectric properties for transformers and high-voltage electrical equipment.
Uninhibited electrical insulating oil for power transformers and switchgear
Produced from highly refined mineral base oils to ensure excellent dielectric performance
Offers long service life with strong resistance to oxidation and sludge formation
Maintains system efficiency through excellent low-temperature flow characteristics (pour point: –57 °C)
Complies with stringent copper corrosion tests including DIN 51353, IEC 62535, and ASTM D1275B
Delivered dry and filtered to maintain high breakdown voltage (>30 kV as delivered, >70 kV after treatment)
Free of polychlorinated biphenyls (PCBs); requires no passivators
Formerly known as: Shell Diala S2 ZU-I non-gasoil tariff
Global Product Code: 001D8373
Shell Diala S2 ZU-I ngt is a premium-quality, uninhibited transformer oil developed for electrical insulation and efficient thermal transfer in high-voltage power systems. It is engineered to deliver long-lasting performance with excellent oxidation resistance and low-temperature fluidity, while meeting rigorous international specifications for copper corrosion and dielectric strength.
| Property | Typical Value | Method |
|---|---|---|
| Appearance | Clear, free from sediment and suspended matter | IEC 60296 |
| Density @ 15 °C | 882 kg/m³ | ISO 3675 |
| Density @ 20 °C | 879 kg/m³ | ISO 3675 |
| Kinematic Viscosity @ 40 °C | 11.0 mm²/s | ISO 3104 |
| Kinematic Viscosity @ –30 °C | 1700 mm²/s | ISO 3104 |
| Flash Point (PM) | 146 °C | ISO 2719 / ASTM D93 |
| Pour Point | –57 °C | ISO 3016 |
| Neutralisation Value | <0.01 mg KOH/g | IEC 62021-1 |
| Corrosive Sulphur (DIN 51353) | Not corrosive | Complies |
| Corrosive Sulphur (IEC 62535) | Not corrosive | Complies |
| Corrosive Sulphur (ASTM D1275B) | Not corrosive | Complies |
| Breakdown Voltage (As Delivered) | >30 kV | IEC 60156 |
| Breakdown Voltage (After Treatment) | >70 kV | IEC 60156 |
| Dielectric Dissipation Factor (DDF) @ 90 °C | 0.002 | IEC 60247 |
| Oxidation Stability – Total Acidity (164 hrs @ 120 °C) | 0.9 mg KOH/g | IEC 61125 C |
| Oxidation Stability – Sludge (164 hrs @ 120 °C) | 0.3 % | IEC 61125 C |
| Oxidation Stability – DDF @ 90 °C (164 hrs) | 0.1 | IEC 60247 |